1. | Embedded plates in concrete for door frame attachment. Acciding to registantion of designs no. 2039795.
T.02 SUPPLEMENTS, CODES, STANDARDS AND QUALITY REQUIREMENTS | | A. | GEMERAL | | Seller shall control the quality of Goods and services to meet the requirements of the requirements of the Specification, applicable codes and standards and other procurement documents. | B. | SUPPLEMENTS | 1. | The supplements listed herein form a part hereof. | 2. | References throughout the Technical Specifications Section or the Design Drawing to specific supplements which are amont those listed herein, and/or to specific Articles or Paragraphs of the supplements listed herein are for convenience only and shall not relieve Seller from all obligations of all requirements of other applicable supplements listed herein, or frfom all other specific.
T.03 SUPPLEMENTS, CODES, STANDARDS AND QUALITY REQUIREMENTS | | C. | INDUSTRY CODE AND STANDARD EFFECTIVE DATE | | All codes and standards shall be the edition in efect as of December 31, 1989, unless indicated otherwise. | |
T.03 SUPPLEMENTS, CODES, STANDARDS AND QUALITY REQUIREMENTS ssss(CONT.) | | D. | INDUSTRY CODES AND STANDARDS | | The WORK shall conform to the applicable requirements of the following documents and applicable supplements (Which are referenced herein and not attached) : | |
SPONSOR | NUMBER | SUBJECT | AISC | | Manual of Steel Construction | ASTM | A 36 | Specification for Structural Steel | ASTM | A607 | Steel, Sheet and Strip, High- Strength, Low-Alloy, Columbium or Vanadium, or both, Hot-Rolled and Cold-Rolled | ASTM | A108 | Steel Bars, Carbon, Cold Finished, Standard Quality | ASTM | D2000 | Rubber Products in Automotive Applications | AWS | A5.1 | Covered Carbon Steel Arc-Welding Electrodes | ANSI/AWS | D1.1 | Structural Welding Code-Steel | SHQAM | Rev.4 | Quality Assurance Manual | ASNT | SNT-TC-1A | Personnel qualification and certification in nondestructive testing | NCIG-01 | | Visual Acceptance Criteria For Structural Welding At Nuclear Power Plants. |
|
T.03 SUPPLEMENTS, CODES, STANDARDS AND QUALITY REQUIREMENTS ssss(CONT.) | | E. | QUALITY REQUIREMENTS | | Work performed under this specification shall be quality class "SHQAM"
T. 04 SUBMITTALS | | A. | DRAWINGS, DATA AND PROCEDURES | 1. | Engineering design calculations, certified by a Registered Professional Engineer, to substantiate that door assemblies are constructed to withstand the specified operating pressures and seismic loads. | 2. | Quality assurance and quality control program. | 3. | Erection Information | | a. Seller shall, when requested, furnish to the Buyer for the erection of the equipment, a detailed scope of the work involved in the complaete erection of this equipment, including all accessories and appurtenances furnished therewith.
b. This information shall include all necessary drawings and a comprehensive outline as to the extent of field fabrication required ; and as to all temporary falsework, scafolding, blocking, shoring, heating, disassembling, reassembling, welding, bolting, cleaning, checking, inspection, painting, testing, etc. required to be done by the Construction Contractor. | 4. | Detailed shop drawings and descriptive data for each type of door assembly, indicating dimensions, fabrication and installation details, materials and finishes. Descriptive data shall include handling, storage and definitive installation instruction, together with complete parts list cross-referenced to drawings. | 5. | Door Manufacturer's specifications, including specifications covering components supplied by Subsuppliers. | 6. | Shop welding methods and procedures. | 7. | Certified Material Test Report including gasket material. | 8. | Welder & Welding Operator Qualification Procedure. | 9. | Nondesturctive examination procedure. | 10. | Spare parts list. | 11. | Handling, storage instruction. | 12. | Technical data for used coating system and manufacturer's name. | B. | QUALITY VERIFICATION REPORTS AND RECORDS | 1. | Seller shall submit a certificate of conformance stating that all work performed under this section meets the requirements of this contract. | 2. | Inspection and test reports shall be submitted to owner in which all characteristics required by the specification appear on a checklist. All inspection and test shall be performed in accordance with the approved Quality Control Instructions and procedures, and the result shall be recorded.
T. 05 DESIGN REQUIREMENTS | | A. | GENERAL | 1. | Doors, frames, and related components and accessories, including hardwares shall be designed, fabricated, and installed to resist the blast pressure and seismic loads specified herein after, acting simultaneously. Doors shall be operable before and after the blast and/or seismic incident. | | |
|
|
|
|
|
|
|
|
|
|
B. | STRESS ANALYSIS AND DESIGN : | 1. | The following design loads and dynamic load factors are to be nsidered. | a. | D = Dead/Gravity Loads. | b. | Po = Normal Operating Pressure : 1/4 inch water gage negative pressure. | c. | Pa = Accident Condition Pressure : 3.0 psi diferential | d. | Ta = Accident Condition Temperature : 523℉ | e. | DLF = Dynamic Load Factor for Accident Pressure : 2.0 | f. | E = Seismic Loads (OBE, SSE) | | Doors shall be designed to withstand the operating Base Earthquake (OBE) and a Safe Shutdown Earthquake (SSE) without failure. Seismic loads are to be calculated utilizing the Response Spectra Curves given in Supplement 1.
Two orthogonal horizontal components and one vertical components shall be considered simultaneously. The vector sum or square root of the sum of the square (SRSS) may be used in combining the seismic stresses in the design. | 2. | The following max. allowable design stresses are to be used : | a. | Noumal loading combination = AISC allowable | b. | Severe environmental loading condition = 1.0 AISC allowable | c. | Abnormal/Severe environmental loading condition and extreme environmental loading condition = 1.6 AISC allowable | d. | Abnormal/Eztreme environmental loading condition = 1.7 AISC allowable | |
T. 05 DESIGN REQUIREMENTS | | | For case c and d, the allowable design stress shall not exceed the following. (1) 0.95 Fy for flexure (2) 0.95 Pcr for compression sss(Pcr is the critical buckling load for elestic or inelastic structural stability) (3) 0.95 Fy/√3 for shear | |
3. | The following loading combinations are to be used : | a. | Noumal combination 1.0 D + 1.0 Po | b. | Severe environmental condition 1.0 D + 1.0 Po + 1.0 EOBE | c. | Extreme Environmental Condition 1.0 D + 1.0 Po + 1.0 ESSE | d. | Abonormal/severe environmental loading condition 1.0 D + 1.0 Pa + Ta 1.0 D + 1.0 EOBE + 1.0 Pa 1.0 D + 1.0 EOBE + 1.0 Ta 1.0 D + 1.0 EOBE + 1.0 Pa + 1.0Ta | e. | Abnormal/Extreme environmental loading condition 1.0 D + 1.0 Pa + Ta 1.0 D + 1.0 ESSE + 1.0 Pa 1.0 D + 1.0 ESSE + 1.0 Ta 1.0 D + 1.0 ESSE + 1.0 Pa + 1.0Ta | | Note : A dynamic load factor (DLF) needs to be applied to Pa as given above. | 4. | Doors shall withstand a maximum blast pressure(static design equivalent), including reflected pressure, of 150psf. | 5. | The maximum allowable leak rate : 0.1 scfm (standard cubic feet per minute) at 3.0 psi diferential. | 6. | The equipment shall remain functional during and after the Design Basis Events specified herein. | 7. | The Seller shall demonstrate the capability of the equipment to sustain the forces resulting from the specified Design Basis Events by qualifying the equipment in accordance with the requirements of Appendix 4I. | 8. | The characteristics of the Design Basis Events are given in the response spectra curves which are included as Attachment A to Appendix 4I. | 9. | The damping factors shall be as follows unless Seller justifies higher values : | | Event | Damping Event Factor | Operating Basis Earthquake | 2 % | Safe Shutdown Earthquake | 5 % |
|
| C. | NAMEPLATE IDENTIFICATION | | Each blast door assembly shall be furnished with stainless steel nameplate mounted on one face of the door, with following information labeled : | 1. | Manufacturer | 2. | Serial job number | 3. | Specification Number | 4. | Tag number (as indicated on door schedule on the drawings).
|
|
T. 07 SHIPPING, HANDLING, STORAGE, PACKING AND MARKING | | A. | GENERAL | 1. | The items procured by this specification are to be shipped, handled, stored, packed and marked in accordance with applicable requirements specified in this specification, manufacturer's published instruction and Part 2.2 of ASME NQA-2, Level B. | 2. | All door assemblies shall be marked and identified with Buyer's door numbers as indicated on paragraph T. 05. C.
T. 08 INSPECTION AND TESTING | | A. | GENERAL | 1. | Seller shall conduct and be responsible for the shop inspections and shop tests called for in the Specification as well as the applicable codes and standards, and shall furnish all facilities necessary for the performance of such tests. | 2. | Buyer has the right to inspect and witness Seller's manufacturing and testing operations for the equipment purchased in accordance with Sections 1 and 2. | 3. | Seller shall submit records and reports for all tests and inspections required by this specification. These records and reports shall be prepared promptly after each test or inspection and shall be transmitted to the Buyer prior to shipment of the equipment to the Project site. | 4. | prior to the release for shipment. | B. | INSPECTION AND TEST | 1. | Shop Testing : Each door unit shall be shop leak tested pneumatically in accordance with ANSI N510 at a pressure diferential of 3.0 psi. Air leakage shall not exceed 0.1 cubic feet per minute per door unit. | 2. | All welds shall be nondestructively examined by magnetic particle or liquid penetrant examination in accordance with procedures and accepted in ANSI/AWS D1.1 Appendix 4K5 or ASME Section IX. Any required grinding of welds shall be done before nondestructive examination (NDE). | 3. | Personnel performing NDE shall be qualified in accordance with ASNT. SNT-TC-1A. | 4. | Nondestructive examination procedure shall be submitted to Buyer for acceptance. Resuits of NDE shall be shipped with the fabricated components. | 5. | Structural steel welds shall be visually examined, unless otherwise specified. Visual examination acceptance criteria for the structural steel welds shall be in accordance with the requirments of NCIG-01 (Rev. 2, May 1985). | 6. | Doors shall be manually operable by normal means, without the use of tools or extra effort after each test. If the assembly fails, it shall be rejected. Rejected assemblies shall be replaced with new ones or reworked to the satisfaction of the Buyer. New or reworked assemblies shall be retested. Gasket materials shall be tested and certified by an indepment testing laboratory to meet all specified conditions. | 7. | Buyer has the right to select any additional test specimens of material being provided and to require tests to be made by the Seller. If the tests prove to be satisfactory, the associated cost will be paid by the Buyer. If the tests prove unsatisfactory, the associated costs will be paid by the Seller. | 8. | Inspection of the material/equipment shall be at the Seller's/Subsupplier's factory. Materials/equipment shall not be prepared for shipment or shipped before the Buyer has either inspected the materials/equipment or waived inspection. The inspection or waiving of inspection by the Buyer at the factory shall in no way relieve the Seller of the responsibility of furnishing materials/ equipment in accordance with this specification. |
|
|
|
|